What Size Radiator Do I Need? Radiator BTU Calculator

Updated 4 min readBy the London Plumbing Supplies counter team

The short answer

Work out the heat the room needs, then choose radiators whose rated output adds up to it. As a quick guide, multiply the room's volume in cubic metres by about 30 W if it's well insulated, 45 W if average or 60 W for solid walls and single glazing, then adjust for room temperature, outside walls and big windows. A 4 × 3.5m living room with a 2.4m ceiling needs about 1,500 W, or 5,200 BTU.

Radiator size calculator

Enter the room's measurements and what it's like. The result is the heat the room needs on a cold day, and the radiator output to look for.

Calculator

Radiator size calculator

A quick estimate from the room's volume, insulation and use. A full heat loss calculation is more accurate.

Heat the room needs

1,512 W

5,159 BTU/h · room volume 33.6 m³

Radiator output to look for

1,512 W

5,159 BTU/h at ΔT50

Shop Type 11, Type 21 or Type 22 radiators.

How to work out radiator size by hand

  1. Multiply length × width × ceiling height in metres to get the room's volume in m³.
  2. Multiply by about 30 W for a well-insulated room (newer build, insulated walls, double glazing), 45 W for an average one, or 60 W for solid walls and single glazing.
  3. Adjust for the room's temperature. The figures above are for a living room at 21°C; bedrooms, kitchens and halls at 18°C need about an eighth less, and a bathroom at 22°C about 4% more.
  4. Add about 10% for a corner room with two outside walls, 20% for three, and take off about 15% for a room with none. Add 15% for large windows or French doors and 10% if it faces north.
  5. Multiply the watts by 3.412 if you want BTU per hour.
Worked examples, with a 2.4m ceiling unless stated
RoomSizeInsulationHeat needed
Living room, one outside wall4 × 3.5m (33.6 m³)Averageabout 1,500 W (5,200 BTU)
Double bedroom3.5 × 3m (25.2 m³)Averageabout 1,000 W (3,400 BTU)
Bathroom2.5 × 2m (12 m³)Averageabout 560 W (1,900 BTU)
Victorian front room, corner, 2.8m ceiling4.5 × 4m (50.4 m³)Solid wallsabout 3,300 W (11,350 BTU) — use two radiators

It's an estimate. A room-by-room heat loss calculation to BS EN 12831, which a heating engineer can do, is the accurate way — and worth having if you're fitting a heat pump.

What does ΔT50 mean on a radiator?

Radiator outputs are quoted at a temperature difference, or Delta T (ΔT), between the water in the radiator and the room. ΔT50 — water averaging 70°C in a 20°C room — is the usual rating. Run the water cooler, as condensing boilers and heat pumps do best, and the same radiator gives out less:

How much of its ΔT50 rating a radiator gives at other temperatures (approximate)
ΔTTypical water temperatureShare of the ΔT50 output
ΔT6080°Cabout 127%
ΔT5070°C100% — the usual rating
ΔT4060°Cabout 75%
ΔT3050°C (typical heat pump)about 51%

So for a heat pump, choose radiators rated at roughly twice the heat the room needs. Always check which ΔT a maker quotes before you compare two radiators — some towel rails are rated at ΔT60, which makes them look a quarter more powerful.

Type 11, 21 or 22?

The type is how many panels and sets of fins a radiator has. A Type 22 gives nearly twice the heat of a Type 11 the same size, so if the wall space is short, go up a type rather than wider. Our Type 11 vs 21 vs 22 guide explains the difference.

Panel radiators on our shelves

Where should the radiator go?

  • Under the window is still the best place in most rooms: it warms the cold air falling off the glass before it crosses the floor.
  • Split big rooms between two radiators on different walls for even heat, and so neither has to be enormous.
  • Keep it clear. A sofa in front or long curtains over the top can cut the heat getting into the room.
  • Fit thermostatic radiator valves (TRVs) so each room holds its own temperature, leaving the room with the wall thermostat on a lockshield or manual valve.

Bathrooms need their heat too: a towel rail covered in towels gives out far less, so check the heated towel rail guide before relying on one alone.

Questions

How many BTU do I need per square metre?
With a 2.4m ceiling, roughly 250 BTU per m² (about 70 W) in a well-insulated room, 370 BTU (about 110 W) in an average one, and 490 BTU (about 145 W) for solid walls and single glazing. Higher ceilings need proportionally more.
Can a radiator be too big?
Not in a harmful way. With a TRV it simply reaches temperature faster and then throttles back. It costs more to buy, but a bigger radiator lets the boiler run cooler and more efficiently.
Do heat pumps need bigger radiators?
Usually, yes. A heat pump runs the radiators at around ΔT30, where they give about half their ΔT50 output, so you need radiators rated at roughly twice the room's heat loss — often by going from Type 11 to Type 22.
What size radiator do I need for a bathroom?
A typical 2.5 × 2m bathroom needs about 560 W (1,900 BTU) at 22°C. Bathrooms are kept warmer than other rooms and have a lot of tiled surface, so don't undersize — and remember towels on a rail cut its output.